Permit Number: T13CM00436
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00436
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
01/24/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied provide outside air balance information for each RTU

mechanical compliance certificates to be for location in Pima County <= 4000 ft. (currently shows >= 4000)
01/24/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/24/2013 LHANLY1 WATER REVIEW Passed
01/24/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.01; APPLICABLE CODES: THE CITY OF TUCSON REQUIRES COMPLIANCE WITH THE FOLLOWING CODES: 2012 IBC, IEBC, IECC, IFC, IFGC, UPC, IPC, AND IMC; 2011 NEC; AND 2009 ICC/ANSI A117.1. REVISE DRAWINGS AS REQUIRED TO MEET THESE CODES.
2. SHEET A0.10; DEMOLITION KEYNOTES: NOTE 7 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A0.11; DEMOLITION KEYNOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET A2.01: PROVIDE A DETAIL ON THE DRAWINGS OF THE BENCH IN THE ACCESSIBLE FITTING ROOM.
5. SHEET A4.01; ELEVATION 12: PROVIDE A VERTICAL GRAB BAR PER FIGURE 604.5.1 OF THE 2009 ICC/ANSI.
6. SHEET A5.01; PARTITION TYPES: PROVIDE BRACING DETAILS OR CALCULATIONS INDICATING THE 10' PARTITION WALL MEETS THE REQUIREMENTS OF THE IBC SECTION 1607.14 FOR A 5 PSF HORIZONTAL LOAD.
7. SHEET A4.05; ELEVATION 6: THE CITY OF TUCSON REQUIRES CALCULATIONS FOR RACKS OVER 12' TALL. PROVIDE. SHOW DETAILS ON THE DRAWINGS FOR THE RACK CONNECTION TO THE FLOOR.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/24/2013 LHANLY1 WWM REVIEW Passed
01/24/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
01/24/2013 JASON GREEN ENGINEERING REVIEW Approved
01/24/2013 ERIC NEWCOMB ADA REVIEW Passed
01/25/2013 MARTIN BROWN FIRE REVIEW Approved
01/29/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review