Permit Number: T13CM00435
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00435
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
01/24/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
01/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/24/2013 LHANLY1 WATER REVIEW Passed
01/24/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.01; APPLICABLE CODES: THE CITY OF TUCSON REQUIRES COMPLIANCE WITH THE FOLLOWING CODES: 2012 IBC, IEBC, IECC, IFC, IFGC, UPC, IPC, AND IMC; 2011 NEC; AND 2009 ICC/ANSI A117.1. REVISE DRAWINGS AS REQUIRED TO MEET THESE CODES.
2. SHEET A0.10; DEMOLITION KEYNOTES: NOTES 15 AND 18 WERE NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A2.01: PROVIDE A DETAIL ON THE DRAWINGS OF THE BENCH IN THE ACCESSIBLE FITTING ROOM.
4. SHEET A4.03; ENLARGED PLAN 6: SEVERAL SECTION CUTS INDICATE SHEET A4.05. REVISE (NO SHEET A4.05).
5. SHEET A4.03; ENLARGED PLAN 5: A SECTION CUT INDICATES SHEET A4.05. REVISE (NO SHEET A4.05).
6. SHEET A5.01; PARTITION TYPES: PROVIDE BRACING DETAILS OR CALCULATIONS INDICATING THE 10' PARTITION WALL MEETS THE REQUIREMENTS OF THE IBC SECTION 1607.14 FOR A 5 PSF HORIZONTAL LOAD.
7. GENERAL: ADD A VERTICAL GRAB BAR IN THE RESTROOM PER FIGURE 604.5.1 OF THE 2009 ICC/ANSI.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/24/2013 LHANLY1 WWM REVIEW Passed
01/24/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
01/24/2013 JASON GREEN ENGINEERING REVIEW Approved
01/24/2013 ERIC NEWCOMB ADA REVIEW Passed
01/24/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/25/2013 MARTIN BROWN FIRE REVIEW Approved