Permit Number: T13CM00406
Parcel: 14108534A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM00406
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the location of the gas pressure regulator and provide specifications for the proposed gas pressure regulator. If required, show how the regulator vent is to be constructed and terminated. Reference: Section 410, IFGC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2013 SHANAE POWELL APPROVAL SHELF Completed
04/26/2013 SHANAE POWELL OUT TO CUSTOMER Completed