Permit Number: T13CM00406
Parcel: 14108534A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00406
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
01/23/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide details to show how the fan coil and the filter fan modules are to be connected to the building structure.
01/23/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM00406

1. The electrical values shown on sheet E-2 do not coinside with what is shown on sheet M2.1 for HP-A or FC-A. There is also a 3.6 kw aux heat supply ?

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
1/23/2013
Ray.Majuta@tucsonaz.gov
01/23/2013 ROBERT SHERRY WATER REVIEW Approved
01/23/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0 (ENLARGED FRAMING PLAN); SECTION 4: ON THE PLAN, NOTE 11 INDICATES 16" WOOD I-JOISTS AT 24" CENTERS, WHILE THE SECTION INDICATES 6" METAL STUDS AT 16" CENTERS. CLARIFY.
2. SHEET A2.0; ENLARGED FRAMING PLAN: PROVIDE A SECTION CUT 4/A2.0 ON THE PLAN.
3. SHEET A2.0; ENLARGED FLOOR PLAN: IN ROOMS 102 AND 103, THERE ARE KEY NOTE SYMBOLS THAT ARE INCOMPLETE. VERIFY.
4. SHEET A2.0; KEY NOTES: KEY NOTES 4, 14, 19, AND 20 WERE NOT LOCATED ON THE PLANS. VERIFY.
5. SHEET A2.0; ENLARGED FLOOR PLAN: AN ENLARGED DETAIL REFERENCE IN THE SOUTH HALLWAY INDICATES 1/A2.0. IS THIS CORRECT?
6. SHEET A2.0; KEY NOTES: A REFERENCE TO KEY NOTE 22 IS ON EACH PLAN, BUT NO KEY NOTE 22 IS LISTED. VERIFY.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/23/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
01/23/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide justification for the use of the sump pump for fixtures that could be gravity-drained. Reference: Section 712.1, IPC 2012.
01/23/2013 MARTIN BROWN FIRE REVIEW Denied Please provide quantities of bottled gases, and indicate how they meet the limits established by the hazardous materials limits in the 2012 International Fire Code. Indicate signage will be provided. Indicate the use of the fume hood(s) and wether or not fire sprinklers will be required.
01/23/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/23/2013 ERIC NEWCOMB ADA REVIEW Passed
01/30/2013 FRODRIG2 WWM REVIEW Approved