Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/31/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | The use of this occupancy appears to be Group I-4. Please revised plans or provide information from the Building Official stating it is not a Group I-4. All required exit signs are not shown. If this is a Group I-4 then occupancy separations may be required, please clarify on plans. A manual fire alarm system is also required for Group I occupancies, please note this on plans. Ken Brouillette CFM Fire Code Administrator |