Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied PREVIOUS REVIEW COMMENT 1:
Please provide 2012 IBC code section that allows the use of swing down bars. Section 1004 and 1004.11.1.1 allows them but for Type "B" dwelling units only.
PREVIOUS REVIEW COMMENT 4:
Please provide an appeal to the building official for a reduced occupancy load as allowed by 2012 IBC, Section 1004.1.2.
END OF RESUBMITTAL REVIEW
01/30/2013 SPOWELL1 WWM REVIEW Needs Review