Permit Number: T13CM00384
Parcel: 13415001F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00384
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2013 TERRY STEVENS ZONING REVIEW Approved
01/22/2013 PAUL MACHADO ENGINEERING REVIEW Approved
01/22/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/22/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1
1. Toilets 1, 2 and 3:
a. Note 28, please reference code allowance for vertical, floor mounted grab bars.
2. Toilets 2 and 3:
a. Note 21 indicates refrigerator
3. Toilet 2:
a. Show urinal to be removed with dashed lines.
4. Define Activity room. It appears to be an assembly with an approximately 80 occupants. Rework occupancy load accordingly. Provide code analysis on drawings.
5. Door 101 with an occupancy load of 50 or more (2 exits required) needs to swing out, 2012 IBC, Section 1008.1.2.
SHEET TS.1
6. Change the 2012 ICC ANSI to the 2009 ICC A117.1.
SHEET A3
7. Detail 5 and 6 show wall mounted swing down grab bars not floor mounted as per note 28 Sheet A2.
END OF REVIEW
01/22/2013 RONALD BROWN ADA REVIEW Passed
01/25/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/25/2013 ROBERT SHERRY WATER REVIEW Approved
01/25/2013 MARTIN BROWN FIRE REVIEW Approved
01/28/2013 FRODRIG2 WWM REVIEW Needs Review
01/28/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved