Permit Number: T13CM00292
Parcel: 10309070A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM00292
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T13CM00292

1. Size conductors and conduits from service to utility, and from MDP to panel H.
2. Provide fault current calculation and let thur values.
3. Previous permit 1/17/2013 showed 100 a service with only parking lot light loads. where did other loads come from ?

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
3/14/2013