Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00292
Parcel: 10309070A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM00292
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T13CM00292

1. Size conductors and conduits from service to utility, and from MDP to panel H.
2. Provide fault current calculation and let thur values.
3. Previous permit 1/17/2013 showed 100 a service with only parking lot light loads. where did other loads come from ?

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
3/14/2013

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2013 CPIERCE1 APPROVAL SHELF Completed
03/18/2013 CPIERCE1 OUT TO CUSTOMER Completed