Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00264
Parcel: 12510006C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM00264
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2013 KEN BROUILLETTE FIRE REVIEW Approved
04/08/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/08/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T13CM00264

Do not yet have access to issued permitted plans, not able to tell what changes are made from previous.
For example, why is the circuit breaker for the 150kva transformer being changed, what was it previuosly ?
Provide a revision sheet describing changes from previous.

Ray T Majuta
Electrical Plan Review
PDSD, Tuscon
4/8/2013
Ray.Majuta@tucsonaz.gov
04/08/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/08/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised floor plan shows the shows a new closet in the surgery room being blocked by the oxygen tanks. Revise as required to provide access to the closet without interfering with the oxygen tanks.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed