Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM00245
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM00245 3002 N Campbell 96.84 KW PV System 1. Provide a detail showing the connection of the conductors of the PV System onto the Metering compartment of the service.Include any information concerning changes that need to be made to the existing service such as drilling bus, bus size, type of terminals conductors using to attach to bus and hardware to be used. Describe the penetration of the conduit as to where it will enter the cabinet. Indicate if room available in compartment for space conductors require. Ray T Majuta Electrical Plan Review PDSD, City of Tucson 2/04/2013 Ray.Majuta@tucsonaz.gov. |
| 02/04/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEETS T1.0 THROUGH E3.1: THE ENGINEER OF RECORD MUST DATE HIS STAMPS ON THE SHEETS AND INCLUDE THE EXPIRATION DATE OF HIS LICENSE. 2. GENERAL: COORDINATE ALL DRAWINGS AND CALCULATIONS THAT ARE INCLUDED FOR THIS PROJECT. CURRENTLY, THERE IS A FULL SIZE SET OF DRAWINGS FOR THE PHOTOVOLTAIC SYSTEM (SITE PLAN WITH ARRAY LAYOUTS, EQUIPMENT ENCLOSURE PLAN, ELECTRICAL DRAWINGS, SOLAR PANEL FRAME CONSTRUCTION AND CONNECTION DETAILS, AND ANOTHER SITE PLAN), AN UNSTAMPED SET OF CALCULATIONS FOR THE PHOTOVOLTAIC SUPPORT SYSTEM, A STAMPED SET OF CALCULATIONS FOR THE PHOTOVOLTAIC SUPPORT SYSTEM (DIFFERENT FROM THE FIRST SET OF CALCULATIONS), STAMPED 8 1/2 X 11 SKETCHES FOR THE TRANSFORMER AND INVERTER PADS, STAMPED 8 1/2 X 11 SKETCHES FOR A CMU SITE WALL, AND A STAMPED SET OF 11 X 17 DRAWINGS FOR THE NORTH AND SOUTH PARKING STRUCTURES. COORDINATE ALL OF THESE, AND SUBMIT A FULL SIZE SET OF STAMPED DRAWINGS THAT INCLUDES ALL PERTINENT DETAILS AND PLANS. 3. GENERAL: VERIFY THE TWO SETS OF SCHNEIDER CALCULATIONS (ONE STAMPED AND ONE NOT STAMPED) ARE REQUIRED. THE SCHLETTER SET INDICATES THE 2006 IBC. 4. GENERAL: THE 8 1/2 X 11 SHEETS WITH SKETCHES SK1, SK2, AND SK3 SUBMITTED BY SCHNEIDER NEED TO HAVE THE DETAILS ON FULL SIZE DRAWINGS. THE GENERAL NOTES INDICATE THE 2006 IBC. 5. GENERAL: THE 8 1/2 X 11 SHEETS WITH S1, S2, S3, S4, AND S5 SUBMITTED BY RICHARD KAISER (DATED 12-28-06) NEED TO HAVE THE DETAILS ON FULL SIZE DRAWINGS. THE GENERAL NOTES INDICATE THE 2006 IBC. 6. GENERAL: THE 11 X 17 SHEETS FOR THE NORTH AND SOUTH PARKING STRUCTURES ARE ACCEPTABLE. HOWEVER, CALCULATIONS FOR THE STRUCTURES MUST BE SUBMITTED. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2013 | CPIERCE1 | REJECT SHELF | Completed |