Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM00227
Parcel: 11714300B

Address:
555 S MEYER AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T13CM00227
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2013 MICHAEL ST. PAUL ZONING REVIEW Needs Review Pemit cannot be issued until after February 14th (see Historic Preservation Case HPZ 13-04.
03/04/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T13CM00227
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and the 2012 International Energy Conservation Code. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. Show a continuous footing for all new exterior walls, R403.1. Include the east wall line, sheet S1.0.

STRUCTURAL PLANS:

1. Provide an engineer's calculation, design and seal for masonry partition and courtyard walls exceeding 7' in height above grade on either side, R301.1. Detail 1/S2.0.
2. Clarify the braced wall sheathing material in compliance with Table R602.10.4 for Wall Type W3.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.

MECHANICAL PLANS:

1. Provide Manual J calculations in accordance with M1401.3, M1601.1, or request a delayed submittal.

ELECTRICAL PLANS:

1. Protect all outlets (except required GFCI circuits) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. Clarify note #23.
2. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.13.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.65, ceiling R=38 and walls R=13. Show these "R" values of insulation at all new construction, or show overall compliance if using less than prescribed component values by providing a RES check calculation N1102.1.
2. Clarify the insulation value notation on sheet A2.0 and A4.0.
3. Both standard and high density R-38 batt insulation requires a space greater than provided with 2" x 8" framing at the Entry. Identify the product that provides the intended value, or provide an appropriate ceiling cavity space.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2013 SHANAE POWELL OUT TO CUSTOMER Completed
03/12/2013 CPIERCE1 REJECT SHELF Completed