Permit Number: T13CM00173
Parcel: 10510062G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM00173
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
01/10/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the operation of the restroom exhaust fans so that recirculation of the air introduced into the restrooms does not occur. Reference: section 403.2.1, IMC 2012.
01/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/10/2013 ROBERT SHERRY WATER REVIEW Approved
01/10/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/10/2013 JASON GREEN ENGINEERING REVIEW Approved
01/10/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide an additional cleanout for each 40-foot section of drains having a change of direction greater than 45 degrees. Reference: Section 708.3.3, IPC 2012.
2. Show that the back-to-back installation of water closets complies with the requirements of Section 706.3, IPC 2012.
3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2012.
4. Provide an approved anti-siphon device (e.g. vacuum relief valve) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2012.
01/10/2013 KEN BROUILLETTE FIRE REVIEW Approved
01/10/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/10/2013 RONALD BROWN ADA REVIEW Passed
01/15/2013 GERRY KOZIOL WWM REVIEW Approved