Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM00173
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/10/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the operation of the restroom exhaust fans so that recirculation of the air introduced into the restrooms does not occur. Reference: section 403.2.1, IMC 2012. |
| 01/10/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/10/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/10/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/10/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/10/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide an additional cleanout for each 40-foot section of drains having a change of direction greater than 45 degrees. Reference: Section 708.3.3, IPC 2012. 2. Show that the back-to-back installation of water closets complies with the requirements of Section 706.3, IPC 2012. 3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2012. 4. Provide an approved anti-siphon device (e.g. vacuum relief valve) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2012. |
| 01/10/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/10/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/10/2013 | RONALD BROWN | ADA | REVIEW | Passed | |
| 01/15/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |