Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2013 MARTIN BROWN FIRE REVIEW Approved
02/27/2013 DAVID RIVERA ZONING REVIEW Approved
03/04/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 9: THE STRUCTURAL CALCULATIONS SHOW A REVISED IBC REFERENCE (AS REQUESTED IN THE FIRST REVIEW). HOWEVER, SHEET E1 OF THE MID-WEST DRAWINGS WAS NOT INCLUDED FOR THIS REVIEW. PROVIDE.
03/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/06/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clearly identify or note on the drawings how the continuous air barrier for the building envelope is to be constructed. Reference: Section 5.4.3.1, ASHRAE 90.1-2010.
2. Verify that the fenestration and doors are labeled and certified by the manufacturer not to exceed the air leakage requirements of Section 5.4.3.2, ASHRAE 90.1-2010.
[Original comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections 101.5 and 101.5.1, International Energy Conservation Code 2012.]