Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM00062
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/27/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 03/04/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 9: THE STRUCTURAL CALCULATIONS SHOW A REVISED IBC REFERENCE (AS REQUESTED IN THE FIRST REVIEW). HOWEVER, SHEET E1 OF THE MID-WEST DRAWINGS WAS NOT INCLUDED FOR THIS REVIEW. PROVIDE. |
| 03/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/06/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clearly identify or note on the drawings how the continuous air barrier for the building envelope is to be constructed. Reference: Section 5.4.3.1, ASHRAE 90.1-2010. 2. Verify that the fenestration and doors are labeled and certified by the manufacturer not to exceed the air leakage requirements of Section 5.4.3.2, ASHRAE 90.1-2010. [Original comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections 101.5 and 101.5.1, International Energy Conservation Code 2012.] |