Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM00016
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a shut off valve for appliances requiring maintenance (e.g. the water filter unit, ice maker). Reference: Section 606.2, IPC 2012. 2. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012. 3. Specify the type of backflow protection to be provided for the water supply to the ice maker. Reference: Section 801.2, IPC 2012. 4. Provide indirect waste piping for the prep sink. Reference: Section 802.1, IPC 2012. |
| 01/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, routing, and termination of the condensate drain for the new 3-ton heat pump. Reference: Sections 307.2.1 and 307.2.2, IMC 2006 as amended by the City of Tucson. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.2, IMC 2012, as amended by the City of Tucson. |
| 01/22/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |