Permit Number: T13BU01328
Parcel: 11615088L

Review Status: Completed

Review Details: TANKS

Permit Number - T13BU01328
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: St. Mary's - Emergency Generator - Fuel Tank
T13BU01328
Plan Review

TRANSMITTAL DATE: March 11, 2014

1. The plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Demonstrate on the plan how the requirements of UDC Article 4.9.10.B.1 are met

3. Per UDC Section 4.9.10.B.2.a A maximum capacity of 1,000 gallons is permitted, proposed is 20,000 gallons.

4. Zoning will re-review the plan on the next submitta.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/03/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
12/19/2013 KEN BROUILLETTE FIRE REVIEW Approved