| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/04/2013 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized electrical repair submittal for COT ID# 325 at 4678 East Broadway Boulevard (T13BU01278). Sheet 1 of 2 1. In Billboard Note #9, delete reference to section 2(x). Sheet 2 of 2 1. In boxed notes, delete reference to section 2(x). 2. Provide documentation of the date of and manner in which the utility pole was destroyed, such as referenced risk manager's report and photographs. 3. Add note referencing the documentation requested in Comment #2 above. |