Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T13BU01042
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/15/2013 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | Sheet 1 of 3 1. In Billboard Note #9, conform the references to Exhibit 9, Section 2 to those on Sheet 2 (add "B" and "G" as applicable). Sheet 2 of 3 1. In South Sign Face Elevation, provide horizontal distances between each outer upright centerline and outer edges of billboard face. 2. In Scope of Work, clarify if angle clips are to be reinstalled or replaced (the reference to Exhibit 9, Section 23(f) would indicate replacement; delete such reference if not being replaced). Sheet 3 of 3 1. Provide standard cross section detail showing mounting of the Z-clips/wood panel section onto the supporting stinger. 2. In North Face and South Face, clarify if the angle clips covered with an "X" indicate locations with existing TEK screws or with no existing TEK screws. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/04/2014 | CPIERCE1 | REJECT SHELF | Completed |