Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
09/03/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair resubmittal for COT ID# 579 at
6101 East Interstate 10 (T13BU00515R).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Revise horizontal dimensions in East Face Elevation so as to match the
overall dimension of 40'0" shown (the dimensions as shown, including 6" for
each of the four beams, add up to 40' 73/4", well in excess of 40'0"; if the
dimensions are not to be measured from the beam centerlines, as requested in
Comment #6 on the original submittal, indicate the beam width dimensions as
well).

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2013 CPIERCE1 REJECT SHELF Completed