Permit Number: T13BU00515
Parcel: 99999999B

Address:
6101 E I10

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T13BU00515
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
05/29/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 579 at
6101 East Interstate 10 (T13BU00515).

Sheet 1 of 3

1. In Billboard Note #9, add "F" and delete "I" (angle clips are shown as
being replaced as to adding "F" and no catwalks are being replaced as to
deleting "I").

Sheet 2 of 3

1. Replacement of backrail shown is not like; revise to show like
replacement.

2. In Note on Exhibit 9, Section 2, add "B" and delete "I"; backrails have
been treated as stringers and no catwalks are shown as to be replaced.

3. Revise the several reference of "catwalk/backrail" to "backrail".

4. Delete phrase in note "some or all components need to be upgraded to
current engineering standards"; the Stipulation does not provide for such
language.

5. In Scope of work, total length of apron of apron stringers (40 ft) does
not match total length of apron pieces (38') and the rendering in East Face
Elevation; revise apron support stringer length to match that of the apron.

6. In East Face Elevation, add horizontal dimensions between upright
centers and between outer upright centers and vertical face panel edges.

7. In East Face Elevation, indicate beam where shim is to be added.

8. Provide known shim dimensions (i.e., those in the horizontal plane that
appear to match the support beam plate).

9. Add note that upright to be removed to add shim to remain on site.

10. In second paragraph of Scope of Work, conform the catwalk width shown
(37") to that shown on Sheet 3 (25.5").

11. In first paragraph of Scope of Work, catwalk ledger length is
excessive; show appropriate length to match standard catwalk (25.5" width).


Sheet 3 of 3

1. In Catwalk Mounting Detail, add horizontal dimensions showing overall
catwalk ledger length and placement of beam faces and catwalk edges relative
to ledger.

2. Add safety cable installation criteria diagram.

3. Add end view for Safety Cable Mounting Detail.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed