Permit Number: T13BU00289
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T13BU00289
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
09/03/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the required modification and authorized repair
second resubmittal for COT ID# 282 at 3646 South Campbell Avenue
(T13BU00289).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. The second resubmittal was not fully responsive to Comment #3 on the
first. Please revise to show the requested special inspection (not only in
the limited case as is now indicated). The removal, reduction in length, and
reinstallation of the unipole can affect the geometry of the structure and
thus the need for a special inspection to check and readjust each of the
light fixtures and associated shields to assure that no light is emitted
above the horizontal plane per the Outdoor Lighting Code.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2013 CPIERCE1 REJECT SHELF Completed