Plan Number: T12PI00008
Parcel: Unknown

Address:
2350 N 1ST AV

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T12PI00008
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2012 BESPINO1 UTILITY CLEARANCES COT STREETS DIVISION Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES QUEST COMMUNICATION Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES COX COMMUNICATION Completed
06/27/2012 BESPINO1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
06/27/2012 BESPINO1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied
06/27/2012 BESPINO1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
07/11/2012 GARY WITTWER DOT LANDSCAPE REVIEW Approved Great Job. Water Harvesting tank --- very nice.
07/11/2012 JOSE ORTIZ DOT TRAFFIC REVIEW Denied ACTIVITY NUMBER: T12PI00008
PROJECT NAME: Walgreens
PROJECT ADDRESS: First Ave & Grant Rd
PROJECT REVIEWER: Matthew Geweke, Traffic Eng Tech

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan. Please include a brief response letter with the next submittal that states how all comments have been addressed.

1. See redlines on the submitted drawing Sht 5 and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.
2. Permits & Codes may also have a concern with the proposed Euclid pork-chop island design: please construct as an all-one-piece/uni-design.


If you have any questions, I can be reached at 791-4259 x76665 or Matthew.Geweke@tucsonaz.gov
07/13/2012 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond I have reviewed these plans and have the following comments:

Sheet 4 - Detail 1/4 - Note 13 is used here and I do not see a sewer manhole at that location.

I would like a copy of the maintenance aggreement for the proposed traffic circle.

No further comments.

Lance
07/19/2012 BLANCA ESPINO PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
07/19/2012 BLANCA ESPINO DOT ENGINEERING REVIEW Approv-Cond 1. Sequence number must be noted for right-of-way dedication along Grant Road.

2. Sheet 2, Detail 1over 2; indicate the 2% cross slope across ingress/egress along Grant Road.
07/19/2012 BLANCA ESPINO PIA COORDINATOR OUT TO CUSTOMER Completed