Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/01/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/23/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments
Below are comments on the electrical repair resubmittal for COT ID# 85 at
5060 East 22nd Street (T12EL00736).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. The engineer's response to Comment #4 on the original submittal
indicates the correction to the panel schedule, but the panel schedule has
been omitted in its entirety from the resubmittal; insert the corrected
panel schedule or otherwise provide a calculation for the load on the single
circuit (including timer control and two light fixtures).

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed