Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12EL00736
Parcel: 99999999B

Address:
5060 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T12EL00736
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the electrical repair submittal for COT ID# 85 at 5060
East 22nd Street (T12EL00736).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Show replacement electrical service (panel, meter, meter socket, riser
conduit & ground) at current location and attached to like replacement of
customer-owned utility pole; provide for same-sized (or NEC minimum)
replacement of existing wire/conduit from service panel on utility pole to
the ballasts on primary billboard structure (new locations of
weatherhead/conduit/ballasts on primary billboard structure accepted as
shown).

2. Provide standard plan (top) view.

3. Conform the note about light fixture removal from the site to that
contained in the Site Plan (Sheet 1).

4. Provide for time control load on one of the two available Panel Schedule
circuits (controller load (shown as 6 v-a max) may already be included in
the v-a calculation as the ballast input calc would otherwise be a total of
625 v-a (250x2x1.25); if so indicate with schedule entry on applicable
circuit).

5. Clarify whether the existing and replacement panels come with the Tork
EWZ103 time controller factory installed or whether the time controller is
shop-installed into the 122MRPS panel; further clarify whether the
manufacturer ships the 122PROG with a 122MRPS or 122PROG exterior
identification plaque (the form of the three notes provided in these regards
for the T12EL00706 resubmittal suffices).

6. Add standard note indicating that no junction boxes or other fixtures
where wire connections are made shall be added or replaced other than those
shown on plan.

7. In the New Electrical Riser Diagram, correct the number of #18 ballast
wires between the two ballast tees (six (6) #18 wires rather than twelve
(12)) or otherwise explain.
12/26/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
12/26/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed