Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12EL00706
Parcel: 99999999B

Address:
4862 S 12TH AV

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T12EL00706
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approved
12/26/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
12/26/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed