Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12EL00706
Parcel: 99999999B

Address:
4862 S 12TH AV

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T12EL00706
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Passed
11/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/27/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair submittal for COT ID# 153 at 4862 South 12th Avenue (T12EL00706).

Sheet 1 of 2

1. Update Billboard Note #4, if applicable.

2. Update Billboard Note #8 to reflect current work.

Sheet 2 of 2

1. Add partial vicinity map.

2. Add standard lamp and ballast descriptions.

3. Add note indicating that no junction boxes or other fixtures where wire connections are made shall be added or replaced other than those shown on plan.

4. Add note that any excess fixtures, conduit, connectors, wiring or breakers no longer being used to be removed.

5. In the Panel Schedule, correct the v-a entries for each lighting circuit to reflect the ballast input power for two HO dual lamp fixtures each plus 125% load factor (BRC calc with Phllips ballast as per prior plan: 248 x 2 x 1.25 = 620) .

6. Indicate 3/4" for incoming service conduit replacement (as like to like; BRC review indicates that existing 3/4" complies with NEC for three #6 wires).

7. Add note clarifying note that time controller to be installed in 206 panel (or otherwise explain; the manufacturer’s literature depiction shows a separate enclosure).

8. Resolve the conflicts on plan where 2006MRPS panel is stated in some instances and 206PROG in others; clarify whether the existing and replacement panels come with the Tork EWZ103 time controller factory installed or whether the time controller is shop-installed into a 206MRPS; further clarify, as applicable, whether the manufacturer ships the 206PROG with a 206 MRPS or 206PROG exterior identification plaque.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2012 SHANAE POWELL REJECT SHELF Completed