Permit Number: T12EL00218
Parcel: 99999999A

Review Status: Active

Review Details: ELECTRICAL

Permit Number - T12EL00218
Review Name: ELECTRICAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12EL00218
795 W Congress St
126.89 KW Photovoltaic System

1. The address is incorrect, the address for the Senior Housing Apartment Complex is 125 S Linda.
2. Need to provide a site plan showing locations of SES-1 and SES 2, all Inverters, Combiners and PV Panels.
3. Provide along with these plans a copy of Structural plans
approved for installation for Panel Modules , from Permit T11CM00617(original Senior Housing Apartments) where these plans where to have been approved.
4. Provide a spec sheet for combiner boxes( including sizes,voltages and amperages) .
5. Provide the following on plans:
total input DC amperages and voltages to inverters,
total output AC amperages and voltages from inverters.
6. Provide conduit sizes for all circuits, "Conduit sizing per
2005 NEC Annex C" insufficient.
7. Provide on plan indication that Identification, Labels,Marking,Plaque and Sign Requirements for Solar PV Systems required per 2005 NEC 690., following Sections, 14,15,16(B),17(4),53,54 and 56, and all others required.


Ray T Majuta,
Elect Pln Review,
PSDS, C of Tuc,
02/12/12
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2012 GERARDO BONILLA REJECT SHELF RECEIVED