Permit Number: T12EL00170
Parcel: 13215001C

Address:
705 E AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12EL00170
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied CLARIFY WHAT PP S1.O IS FOR. WHAT DOES THIS FOUNDATIN APPLY TO AND WHERE IS IT IN SITE PLAN? ALSO WHERE IS REST OF CANOPY DETAIL?

PROVIDE CALCULATIONS FOR LIGHT POLE BASES, OR PROVIDE CUT SHEETS FOR SAME FROM MANUFACTURER.
03/09/2012 TERRY STEVENS ZONING REVIEW Approved