Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
01/12/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/18/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair plan submittal for COT ID# 137
at 6959 East Broadway Boulevard (T12EL00033).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Correct the vertical measure dimension of the face panels referenced in
the title block.

2. Specify the particular model number of the time control in the Tork EWZ
series to be
installed.

3. Clarify the circuit that the time control is powered by.

4. In the panel schedule, the stated amperage does not appear to account
for the additional load required for the ballast on each circuit (in the
case of the stated ballast, the input power is 250 watts per fixture
according to manufacturers literature, or a minimum entry of 625A with the
125% demand factor included).

5. Add note that no junction boxes or other fixtures where wire connections
are made to be installed other than those depicted on plan.

6. Add note that any excess fixtures, conduit, connectors, wiring or
breakers no longer being used to be removed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2012 GERARDO BONILLA OUT TO CUSTOMER Completed