Permit Number: T12CM08260
Parcel: 11706168A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM08260
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed; no details have been submitted by the architect or structural engineer. [Original comment: Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2006.]
03/01/2013 ROBERT SHERRY WATER REVIEW Denied Comment not resolved; the shell work (T12CM07950) is in a "Returned for Corrections" status. Provide a reference copy of the drawing that shows the requested information. [Original comment: Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Indicate the demand that the water meter will be serving. Reference: Section 103.2.3, UPC 2006.]
03/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2013 SHANAE POWELL OUT TO CUSTOMER Completed
03/27/2013 CPIERCE1 REJECT SHELF Completed