Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM08252
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/18/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Somewhere in the plumbing drawings, details and statements needs to be included to clarify that the water heater is wall mounted and refered to the structural drawings for details and calculations. Detail 2/P1.2 seems to be the most logical place for this requirement however it is clearly showing a floor mounted system. Please modify detail 2/P1.2 to diagramaticly show a wall mounted water heater and refer to the structural details. 2. As per your Sheet Index on sheet A-1.0, Sheet P1.0 is missing and Sheet P1.1 is not included. Please reconcile. END OF REVIEW |
03/18/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; absent a structural issue, each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally (see P-1 and P-2 in the bar, room 103). [Original comment: Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally. Reference: Section 905.3, UPC 2006.] 2. The dishwasher, K-85, is a now a low-temperature unit that requires only 140 degree water; where does detail 3/P1.2 apply? |
03/18/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The submitted shop drawings show a zero-clearance Type I hood but nothing in the specifications includes this requirement. [Original comment: Verify that the Type I hood installation complies with Section 507.9, IMC 2006 for clearances. Wall type F calls for plywood backing and the J (stainless steel panels) notation for the wall covering does not indicate the extent of the wall covering (also, what is a "bar die" wall?).] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/27/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
03/27/2013 | CPIERCE1 | REJECT SHELF | Completed |