Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM08244
Parcel: 11712087C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM08244
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Please provide structural details and calculations for the new operatable wall system tracks.
04/26/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the connection point for the horizontal drain from room 406 to the lower level; second floor (as noted) or the floor below? Reference: Sections 310.0 and 314.5, UPC 2006.]
04/29/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the ventilation calculations for VRF unit 5-1E and remove the duplicate calculations for VRF units 4-3E, 4-5E, 5-5E, and 5-7E (there are 4 copies of 5-7W).
2. Clarify the outside air intake for VRF 4-1W: if the air flow rate shown as "30% increase (EQc2)" is being used to determine the minimum outside air intake, why is the scheduled minimum outside air flow rate less than the calculated outside air flow rate?
3. Clarify the equipment tags for the energy recovery units and reconcile the balancing data with the VRF units. The drawings show ERU-1 on the 4th floor and ERU-2 on the 5th floor but the schedule calls out ERU-3 and ERU-4.
05/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM08244
1 East Broadway

1. Sheet E-102 shows Panels for the 3rd and 4th floors no 5th floor panels. Several power, lighting and HVAC circuits are shown going to the 5th floor panels. Provide Panel Schedules for 5th floor Panels.
2. Sheet E-205 showing circuits 4A 34,36 to AC-1 and
4A 38,40. Panel 4A panel schedule has these circuits going to other items.
3. Sheet E-201 shows power plan layout for 3rd fl West,
Sheet E-202 shows power plan layout for 3rd fl East,
Sheet E-203 shows power plan layout for 5th fl West,
Sheet E-204 shows power plan layout for 5th fl East,
Sheet E-205 shows Roof Plan eqpmt for 4th and 5th fls,
Sheet E-301 shows lighting plan for 4th fl West
Sheet E-302 shows lighting plan for 4th fl East,
Sheet E-303 shows lighting plan for 5th fl West,
Sheet E-304 shows lighting plan for 5th fl East,
Sheet E-401 shows special systems 4th fl
Sheet E-402 shows special systems 5th fl,
Sheet E-102 and E-103 show panel and schedules for 3,4
What has happened to panels and schedules for 5th fl, and will there be no power on 4th fl just lighting? I am aware one floor has been renumbered, does the panel and schedule need to be renumbered for panels also ?

Ray Majuta
Elect Plan Review
PDSD, City of Tucson
5/6/2013
Ray.Majuta@tucsonaz.gov
520-837/4988

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2013 CPIERCE1 REJECT SHELF Completed