Permit Number: T12CM08244
Parcel: 11712087C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM08244
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2013 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
04/22/2013 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
04/22/2013 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
04/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12cm08244

1. Provide a revision sheet indicating changes made and reason for changes. Appears the changes involve renumbering the room numbers and floor numbers.
Sheets E-203 and 204, the circuits have been relocated to the 5th floor panels, however the panel schedules for the
5th floor not provided ?

Ray Majuta
Elect Plan Review
DSD, Tucson
4/22/2013