Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM08244
Parcel: 11712087C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM08244
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2013 KEN BROUILLETTE FIRE REVIEW Approved
01/11/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Provide structural calculations and details for:
a. All new roof mounted HVAC equipment
b. All new suspended fan coil units
SHEET A301
2. Insure all exposed lavatory is insulated as per ICC A117.1, Section 606.6.
END OF REVIEW
01/11/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed Already paid as per LeeRay LHM Notice
01/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for plumbing fixtures P-9, P-10, and P-11, as shown on sheet P101. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). If P-9 is an indirect waste receptor, verify that its location complies with the requirements of Section 804.1, UPC 2006. Reference: Sections 301.1.1 and 401.1, UPC 2006.
2. Revise the description of water closet P2A to remove the portions of the description that are intended for the lavatory, P-1A.
3. Provide a design for the mounting shelves for the water heaters along with structural calculations to show that the water heaters are safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
4. Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally. Reference: Section 905.3, UPC 2006.
01/18/2013 ROBERT SHERRY WATER REVIEW Approved
01/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
2. Provide information regarding the nature of the exhaust discharge from the slotted hood and show that the location of the exhaust outlet complies with the requirements of Sections 501.2, 501.2.1, and 502.7, IMC 2006.
3. Show how adequate make up air will be provided to the room containing the slotted exhaust hood when the hood is operating. Reference: Section 501.3, IMC 2006.
01/29/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2013 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2013 SHANAE POWELL REJECT SHELF Completed
02/01/2013 CPIERCE1 OUT TO CUSTOMER Completed