Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM08244
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/07/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
01/11/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Provide structural calculations and details for: a. All new roof mounted HVAC equipment b. All new suspended fan coil units SHEET A301 2. Insure all exposed lavatory is insulated as per ICC A117.1, Section 606.6. END OF REVIEW |
01/11/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | Already paid as per LeeRay LHM Notice |
01/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide fixture descriptions for plumbing fixtures P-9, P-10, and P-11, as shown on sheet P101. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). If P-9 is an indirect waste receptor, verify that its location complies with the requirements of Section 804.1, UPC 2006. Reference: Sections 301.1.1 and 401.1, UPC 2006. 2. Revise the description of water closet P2A to remove the portions of the description that are intended for the lavatory, P-1A. 3. Provide a design for the mounting shelves for the water heaters along with structural calculations to show that the water heaters are safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 4. Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally. Reference: Section 905.3, UPC 2006. |
01/18/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/18/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 2. Provide information regarding the nature of the exhaust discharge from the slotted hood and show that the location of the exhaust outlet complies with the requirements of Sections 501.2, 501.2.1, and 502.7, IMC 2006. 3. Show how adequate make up air will be provided to the room containing the slotted exhaust hood when the hood is operating. Reference: Section 501.3, IMC 2006. |
01/29/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/01/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/04/2013 | SHANAE POWELL | REJECT SHELF | Completed |
02/01/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |