03/15/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM08243
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and the 2012 International Energy Conservation Code. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R319.1 item 5. Clarify Detail #1/d1.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d. Clarify Detail #7/d2.
3. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
4. Provide consistent information for the vented attic space, R806.4. Remove the insulation from the roof underside at Section #1/a4.

PLUMBING PLANS:

1. Show accessibility for servicing the water heater, UPC 505.3.1.
2. Gray water systems in compliance with the City of Tucson Ordinance #10579 and the Arizona Department of Environmental Quality publication #C07-01 are only required for a new dwellings rather than an addition to an existing dwelling.
3. When designing a gray water system with diverter valves include a collection tank with an overflow connection to the black water line if a is included. Furthermore, include a backflow valve on the water meter connection. Show an electrical circuit for a system pump.
4. The clothes washer must have a discharge to the building drainage system. Show dual clothes washer standpipes if including a gray water option. Provide one discharge opening plumbed to an exterior wall with an above grade stub-out for gray water surface distribution. Provide a second discharge opening plumbed to the building black line in compliance with the City of Tucson Ordinance #10579.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R313.2. Show a smoke alarm on the outside of the bedroom door.
2. Sheet #a1 shows a new exterior dining room wall. Show receptacle outlets (interior side) at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3801.2.
3. Protect bedroom outlets including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3802.12.

OUTDOOR LIGHTING CODE

1. Show the proposed fixtures as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the maximum "U" factors of the windows and doors on the plans, N1102.1. Clarify insulation information shown on sheet a1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review