Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM08236
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/23/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S1.0 (SECTION 201); STRUCTURAL CALCULATIONS (SHEET 1): SECTION 201 DOES NOT PROVIDE THE COLUMN SIZE FOR THE EXTENSION. THE STRUCTURAL CALCULATIONS DO NOT GIVE A COLUMN SIZE FOR THE EXTENSION. PROVIDE THE COLUMN SIZE (OR REFERENCE) FOR THE EXTENSION ON SECTION 201 AND DETAIL 202/S1.1. 2. SHEET S1.1; FRAMING PLAN: BETWEEN GRIDS 3 AND 4, A SECTION CUT NEEDS TO BE COMPLETED. VERIFY. 3. SHEET S1.1; DETAIL 202: NOTE 5 INDICATES WEB STIFFENERS, BUT IS POINTING TO THE COLUMN. REVISE AND CALL OUT THE COLUMN EXTENSION. 4. GENERAL: PROVIDE STRUCTURAL CALCULATIONS (ON 8 1/2 X 11) AND DETAILS (ON FULL SIZED SHEETS) FOR THE CONNECTION OF THE PHOTOVOLTAIC PANELS TO THE STRUCTURE. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/28/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2013 | CPIERCE1 | REJECT SHELF | Completed |