Permit Number: T12CM08207
Parcel: 136291460

Review Status: Completed

Review Details: WALK THRU - RES

Permit Number - T12CM08207
Review Name: WALK THRU - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Approved 1. 2x4 rafters spaced 24" on center spanning 11'6" are not an approved support for the proposed mechanical unit. Note: an engineer is required to verify new equipment on existing engineered roof framing systems.

2. Provide ACCA Manual S based on building loads calculated in accordance with ACCA Manual J