Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM08196
Parcel: 130130670

Address:
3601 E 34TH ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM08196
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond RAPID ENTRY REQUIRED FOR THE GATES AND FIRE EXTINGUISHERS WILL BE REQUIRED
01/10/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied COVER SHEET
1. Please provide structural calculations for the 10' high fence.
2. Please provide code analysis for non-separated use, Section 503.3.2.
SHEET S0
3. Please provide certification for special inspectors.
GENERAL
4. Please provide a typical wall section showing all materials including exterior and interior wall systems and materials.
5. Please show exterior wall finish on all exterior elevations.
END OF REVIEW
01/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A note on sheet E-1 states that the evaporative coolers are "…existing to be replace (sic)". If the garage is new, how did the evaporative coolers exist on a nonexistent building? Reference: Section 103.2.3, UPC 2006.
2. Provide sufficient information to show that the connection point of the water service for the new evaporative coolers will not cause the part of the existing water supply system to become overloaded. Reference: Section 101.5.1, UPC 2006.
3. Provide the dimensions of the roof drains indicated on sheet A-1 and clarify their actual nature, i.e. drains or scuppers.
4. What is the material being used for the water service to the evaporative coolers? Reference: Section 604.0, UPC 2006.
5. Clarify the routing of the water service to the evaporative coolers (i.e. above or below the roof) and indicate how the piping will be protected from freezing. Reference: Sections 313.5 and 313.6, UPC 2006.
01/16/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the rooftop equipment. Reference: Sections 106.3.1and 301.6, IMC 2006.
2. Show how access is being provided to the evaporative coolers. Reference: Section 306.5, IMC 2006.
3. Show how drainage is being provided for the evaporative coolers. Reference: Section 304.1, IMC 2006.
4. Clarify the slope of the roof, 1/8" per foot or 3/8" per foot; both are shown on sheet A-1.
01/16/2013 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter and the backflow preventer serving the existing building and this addition.
01/25/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM08196
New Garage

1.NEC 2005 511- Commercial Garages, requires certain areas to be considered as Classified Locations , these areas require special wiring and equipment per 511.3. Indicate on plan if repair area is Unclassifed or Classified per 511.3.A.
Then indicate which Area is to be followed in wiring and installation of electrical equipment.
2. All receptacles to be GFI protected as per 511.12
3. The receptacles shown in the 227/480 volt panel not shown in plan, these should be of a special type, please indicate on plan type to be used.
4. The voltage listing for Panel G is 120/240 volt 3 phase, this would indicate Phase B would be a high leg, should be 120/208 volt 3 phase.
5. The flood lights on the outside corner of building should be Full Cut Off, unless a Lumen count of the entire site is provided for allowing un-shielded light per City of Tucson Outdoor Lighting Code 2012, provide light fixture spec's.
6. Since the 277/480 volt Panel is new, need to verfy the 10,00 0AIC rating is sufficient.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
1/25/2013
Ray.Majuta@tucsonaz.gov
02/05/2013 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2013 GERARDO BONILLA APPROVAL SHELF Completed
11/01/2013 GERARDO BONILLA OUT TO CUSTOMER Completed
11/01/2013 CPIERCE1 REJECT SHELF Completed