Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM08196
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | RAPID ENTRY REQUIRED FOR THE GATES AND FIRE EXTINGUISHERS WILL BE REQUIRED |
| 01/10/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | COVER SHEET 1. Please provide structural calculations for the 10' high fence. 2. Please provide code analysis for non-separated use, Section 503.3.2. SHEET S0 3. Please provide certification for special inspectors. GENERAL 4. Please provide a typical wall section showing all materials including exterior and interior wall systems and materials. 5. Please show exterior wall finish on all exterior elevations. END OF REVIEW |
| 01/16/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A note on sheet E-1 states that the evaporative coolers are "…existing to be replace (sic)". If the garage is new, how did the evaporative coolers exist on a nonexistent building? Reference: Section 103.2.3, UPC 2006. 2. Provide sufficient information to show that the connection point of the water service for the new evaporative coolers will not cause the part of the existing water supply system to become overloaded. Reference: Section 101.5.1, UPC 2006. 3. Provide the dimensions of the roof drains indicated on sheet A-1 and clarify their actual nature, i.e. drains or scuppers. 4. What is the material being used for the water service to the evaporative coolers? Reference: Section 604.0, UPC 2006. 5. Clarify the routing of the water service to the evaporative coolers (i.e. above or below the roof) and indicate how the piping will be protected from freezing. Reference: Sections 313.5 and 313.6, UPC 2006. |
| 01/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the installed weight of the rooftop equipment. Reference: Sections 106.3.1and 301.6, IMC 2006. 2. Show how access is being provided to the evaporative coolers. Reference: Section 306.5, IMC 2006. 3. Show how drainage is being provided for the evaporative coolers. Reference: Section 304.1, IMC 2006. 4. Clarify the slope of the roof, 1/8" per foot or 3/8" per foot; both are shown on sheet A-1. |
| 01/16/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter and the backflow preventer serving the existing building and this addition. |
| 01/25/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM08196 New Garage 1.NEC 2005 511- Commercial Garages, requires certain areas to be considered as Classified Locations , these areas require special wiring and equipment per 511.3. Indicate on plan if repair area is Unclassifed or Classified per 511.3.A. Then indicate which Area is to be followed in wiring and installation of electrical equipment. 2. All receptacles to be GFI protected as per 511.12 3. The receptacles shown in the 227/480 volt panel not shown in plan, these should be of a special type, please indicate on plan type to be used. 4. The voltage listing for Panel G is 120/240 volt 3 phase, this would indicate Phase B would be a high leg, should be 120/208 volt 3 phase. 5. The flood lights on the outside corner of building should be Full Cut Off, unless a Lumen count of the entire site is provided for allowing un-shielded light per City of Tucson Outdoor Lighting Code 2012, provide light fixture spec's. 6. Since the 277/480 volt Panel is new, need to verfy the 10,00 0AIC rating is sufficient. Ray T Majuta Elect Plan Review PDSD, City of Tucson 1/25/2013 Ray.Majuta@tucsonaz.gov |
| 02/05/2013 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/01/2013 | GERARDO BONILLA | APPROVAL SHELF | Completed |
| 11/01/2013 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 11/01/2013 | CPIERCE1 | REJECT SHELF | Completed |