Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM08177
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide roof drainage calculations and provide the dimensions of the scupper. |
| 12/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | revise the envelope energy calculations to include the window. Show the required U-value and SHGC for the window on the plans. |
| 12/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/27/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/28/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 12/28/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 12/28/2012 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/28/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/28/2012 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/28/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 12/28/2012 | CPIERCE1 | ADA | REVIEW | Needs Review |