Permit Number: T12CM08171
Parcel: 117132170

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM08171
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a9.0; Details 3, 6, and 17: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
2. Sheet a9.1; Details 23, 24, and 26: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
3. Sheet s3.0 (Detail 210); Structural Calculations (Sheet 17): The calculations indicate a 5x5x3/8 angle support, while Detail 210 indicates a 5x5x5/16 angle (note 4). Please clarify.
04/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/04/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change There was no correction or comment response to comment #5, last plan review,"#5. Provide full compliance with the IECC for interior lighting". Please see sec.C405 of the 2012 IECC.
05/17/2017 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2019 SBEASLE1 OUT TO CUSTOMER Completed