Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM08171
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet a9.0; Details 3, 6, and 17: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 2. Sheet a9.1; Details 23, 24, and 26: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 3. Sheet s3.0 (Detail 210); Structural Calculations (Sheet 17): The calculations indicate a 5x5x3/8 angle support, while Detail 210 indicates a 5x5x5/16 angle (note 4). Please clarify. |
| 04/27/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/27/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/04/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | There was no correction or comment response to comment #5, last plan review,"#5. Provide full compliance with the IECC for interior lighting". Please see sec.C405 of the 2012 IECC. |
| 05/17/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/30/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |