Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM08171
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/02/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Label all pipe sizes. Reference: Section 107.2.1, IBC 2012. 2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. 3. Verify the size of the horizontal drain (4" W BF) shown on plumbing plan 2/p1.1. If it is 4", provide a 4" cleanout. Reference: Section 708.7, IPC 2012. 4. Revise detail 1/p1.2 so that the minimum font size is 1/32" and the detail is legible. Clarify all notes on the detail that refer to "optional" accessories or "minimum" pipe sizes; state what is required. Reference: Section 107.2.1, IBC 2012. 5. Verify the total connected gas load; it is 435CFH on sheet p1.1 and 407 CFH on sheet p1.2. Reference: Section 107.2.1, IBC 2012. |
03/02/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/02/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the dryer installation complies with Section 504.5, IMC 2012. |
03/22/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Lettering font size must be 3/32" minimum. #2. There appears to be printing errors making the registrant seal and areas thru-out the plans non legible. #3. The panel schedule for panel 4H1 shows "New Panel", however the riser diagram shows it as existing. Please correct this. #4. Please provide commentary as to the changes. The reference electrical plans include four plan sheets, making reference to Phase 1 and Phase 2 of this project. #5. Provide full compliance with the IECC for interior lighting. Ref: IBC sec. 107.2.1 |
03/31/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: IT APPEARS EVERY ARCHITECTURAL AND STRUCTURAL SHEET HAS BEEN REVISED (PER SHEET a1.0 INDEX). PLEASE PROVIDE A LIST OF ALL SHEET REVISIONS, SPECIFICALLY INDICATING ALL CHANGES ON EACH SHEET (CLOUD ALL CHANGES). 2. GENERAL: INDICATE ALL REVISIONS TO THE STRUCTURAL CALCULATIONS AND INDICATE CALCULATION SHEET NUMBERS. 3. GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/10/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |