Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM08171
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 12/27/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/27/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the plumbing code to be used for this activity. The plumbing specifications on sheet p1.2 refer to the 2006 UPC but the project data section on sheet a1.0 refers to the 2006 IPC. This review has been made using the 2006 UPC. 2. Verify that the installation of the water heater, expansion tank, and the recirculating pump comply with the manufacturers' specifications for clearances. Reference: Section 310.4, UPC 2006. 3. Show the route and termination of the T&P relief and the pan drain. 4. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 401.1, UPC 2006. |
| 12/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/31/2012 | LHANLY1 | FIRE | REVIEW | Approved | separate permits required for any required sprinkler changes and for alarms. |
| 12/31/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |