Permit Number: T12CM08107
Parcel: 99999999A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM08107
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2013 RONALD BROWN ADA REVIEW Passed
01/10/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T12CM08107
Building Plan (1st Review)

TRANSMITTAL DATE: January 10, 2013

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the tenant improvement plan and it appears that the plan matches the shell building plan.

3. Once the shell building plan has been approved zoning will approve the tenant improvement plan.

3. Zoning will re-review the plan on the next submittal to insure compliance.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/11/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied H100
1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 106.3.1 and 301.2, IPC 2006.
2. Provide fixture descriptions for all plumbing fixtures (these were not included in the specifications). Reference: Section 402, IPC 2006.
3. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006.

H105
1. Provide fixture descriptions for all plumbing fixtures (these were not included in the specifications). Reference: Section 402, IPC 2006.
2. Revise the riser diagrams referenced for the restroom from "B" to "C" to coordinate with the fixture layout in the plumbing plan.
3. Show that the back-to-back installation of water closets (Diagram "C") complies with the requirements of Section 706.3, IPC 2006.

H106
1. Provide fixture descriptions for all plumbing fixtures (these were not included in the specifications). Reference: Section 402, IPC 2006.
2. Revise the riser diagrams referenced for the restroom from "B" to "C" to coordinate with the fixture layout in the plumbing plan.
3. Provide hot water for the mop sink. Reference: section 607.1, IPC 2006.
4. Show that the back-to-back installation of water closets (Diagram "C") complies with the requirements of Section 706.3, IPC 2006.
5. Provide cleanouts sized per Section 708.7, IPC 2006 (see waste and vent diagram "D").
01/14/2013 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
01/17/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
01/17/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (4), IMC 2012.
2. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012.
01/17/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PROVIDE IECC LIGHTING COMPLIANCE CERTIFICATE
01/17/2013 LHANLY1 WATER REVIEW Denied
01/17/2013 LHANLY1 FIRE REVIEW Approved SEE RELATED ACTIVITY T12CM08106
01/17/2013 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/05/2013 GERRY KOZIOL WWM REVIEW Denied NEED TO PERMIT
NEED TYPE III SEWER CAPACITY LETTER FOR SHELL
NEED TO SHOW ON DRAWINGS

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2013 CPIERCE1 REJECT SHELF Completed