Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM08100
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM08100
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2013 RONALD BROWN ADA REVIEW Passed 2010 ADASAD review to be included in Building Code Compliance Review
01/07/2013 KEN BROUILLETTE FIRE REVIEW Approved
01/09/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL:
1. For all plans showing new ramps and/or stairs, please reference from each different type of ramp/stair a large scale plan detail showing all accessible requirements such as dimensions, elevation changes, riser and tread dimensions, handrails, slopes and landings.
a. Reference from these larges scale plan details a large scale elevation of all the different types of handrails.
b. If no large scale plan or elevation exists, please provide one.
2. For all existing ramps receiving new accessible handrails, provide a reference to a large scale handrail elevation. If none are detailed already, please provide one and reference to it.
3. Please provide certification of the special inspectors for approval.
COVER SHEET
4. As per the 2006 IEBC, Section 605.2, Exception 1, the costs of...are not required...to exceed 20% of the alterations. "Alterations" as defined by Section 202 does not include furniture. Please delete any furniture costs included in the 20% calculation and include it as building construction alteration costs.
SHEET A2.1
5. Ditto Comment 1
6. Reference the exterior ramp to the large scale ramp detail 2/A1.0.
7. Add elevation mark +24" at corridor 60A.
8. Provide elevation reference markers for the Break Room 62.
SHEET A2.2
9. There are a couple of revision markers referencing to detail section 1/101. I can not find sheet 101 in the Index or the set of drawings. Please reconcile.
10. Ditto comment 1.
SHEET A2.3
11. Please provide elevation changes of the ramp.
SHEET A2.4
12. Ditto Comments 1 and 2
13. At detail 2:
a. Provide 18" clear on the strike side of both entrance doors from the inside as required by the 2010 ADASAD, Section 404.2.4.1.
b. The free standing floor waste receptor is encroaching upon the 5' clear floor space turn around in both toilet rooms and in the men's room accessible lavatory clearance space.
c. Reference all interior elevations to the interior elevations already drawn and provide additional ones if not shown for all toilet room elevations.
SHEET A2.7
14. Ditto Comment 1
SHEET A5.0 AND A5.1
15. Insure that all handrail elevations detailed here are reference from the respective ramp and stair plans.
16. At details 4 and 6/A5.0, sink counter tops are to be a maximum of 2'-10" a.f.f. as required by Section 606.3
SHEET S1.0
17. Provide structural calcs for all new roof top mounted and/or suspended HVAC equipment and all wall mounted water tanks, hot or expansion water tanks.
END OF REVIEW
01/15/2013 ROBERT SHERRY WATER REVIEW Approved
01/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the detail titles on sheet P2.2.
2. Clarify how the sinks P-3 and P-6 are connected to the drain system in detail 2/P1.0. Reference: Section 103.2.3, UPC 2006.
3. Clarify how the temperature mixing valves, TMV-1 and TMV-2, are to be integrated into a recirculating hot water system; detail 205 addresses a point-of-use application only. The manufacturer states that this particular type of mixing valve should not be used for temperature control at the hot water source in a recirculating system due to the risk of bacterial growth in the piping if the water circulates at a temperature less than 140 degrees Fahrenheit. In addition, the specified mixing valves are not listed to ASSE 1016 as shown in the fixture specifications. Reference: Section 310.4, UPC 2006.
4. Clarify how TMV-1, as shown in detail 2/P1.1, is able to accommodate the connected load of two showers, four lavatories, a 2-compartment sink, and a mop sink. Mixing valve TMV-2, as shown in detail 2/P1.1, is similarly installed. In both cases, the specified mixing valves will see a demand of 10 GPM and have a pressure drop of approximately 28 PSI. Reference: Sections 310.4 and 608.1, UPC 2006.
5. Provide shower control valves that comply with the requirements of Section 418.0, UPC 2006.
6. In detail 2/P1.0, a new 3" drain is connected to an existing 4" building drain but no 4" cleanout is shown. Provide cleanouts sized per Section 707.11, UPC 2006.
7. Clarify how the ice machine, P-10, and its backflow preventer will be able to drain using gravity flow to the specified washer box, P-10A. Reference: Section 804.1, UPC 2006.
8. Coordinate the total connected load for the gas meter shown on the plumbing plans and the gas diagram with the gas meter load (Phase 2). Reference: Section 1209.1, UPC 2006.
01/16/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/05/2013 GERRY KOZIOL WWM REVIEW Denied NEED TO IDENTIFY SIZE & NUMBER OF EXISTING WATER METERS FOR SEWER FEE CALCULATION REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2013 CPIERCE1 OUT TO CUSTOMER Completed
02/28/2013 CPIERCE1 REJECT SHELF Completed