Permit Number: T12CM08060
Parcel: 129020510

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM08060
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2013 KEN BROUILLETTE FIRE REVIEW Reqs Change The proposed electric hot plates appears to need a Type I hood. Please make an appeal to the Building Code Official if you feel that this does not apply to the use of this hot plate.
02/25/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approv-Cond Mechanical approved based upon the approval of an Appeal to the Building Official to allow the use of a Type II hood over a discrete-element electric cooktop.