Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM08060
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. A restaurant (A2) with an occupancy load of less than 50 shall be classified as a (B) business as per the 2006 IBC, Section 303.1, Exception 1. Please change the building classification on your code summary to "B". 2. Please provide structural details and calculations for the following: a. The new roof top mounted HVAC unit. b. The new type II exhaust hood. END OF REVIEW |
| 01/09/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/11/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the tags for the existing and the new rooftop A/C units: in detail 02/M1.0, both are labeled as AC-1; on sheet M3.0, the new unit is shown as both AC-1 and as AC-2. 2. Verify that a separation of at least ten feet exists between the air intake opening for the new "AC-1" and the exhaust opening for EF-1. Reference: 401.4.1, IMC 2006. 3. Verify that the amount of outside air introduced into the building is not significantly less than the amount of air being exhausted from the building (i.e. will both A/C units be interlocked with the Type II hood). Reference: Section 403.1, IMC 2006. |
| 01/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/29/2013 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/27/2012 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Please refer to 2006 IBC 303.1 Exception 1. This should be a Group B Occupancy |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/07/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 02/07/2013 | CPIERCE1 | REJECT SHELF | Completed |